Industrial Batteries :  


 SWITCH TRIPPING UNIT :

A. Introduction:­

 

All the models of Battery Chargers shown in the pictures are commanly used in Electric Power Sub-Stations to operate the Tripping Coils of OCB's and they are known as Switch Tripping Units.

The Switch Tripping Units are made in two basic Models:
  1. With Battery Enclosure and
  2. Without Battery Enclosure
    The DC DB (i.e. DC Distribution Board ) can be provided  in both the versions.



All standard indications and protections provided such as Over Charging Protection, Short Circuit Protection, Over Load Protection etc.

The Battery Charger Unit is made in 'Z' Section C.R.S. Sheet Metal Cabinet with suitable Angle frame for Battery Mounting & Provided with adequate ventilation. The Battery compartment is sealed off from the charger section and is specially treated to withstand Acid Fumes. The entire cabinet is coated with Grey Export Stoving Paint.  
 B. Technical Specifications:
MODEL

IBC-24 V

IBC-30 V

IBC-110 V

INPUT VOLTAGE

230 V 1 PH 50 HZ

230 V 1 PH 50 HZ

415/440 V  3 PH

BATTERY CAPACITY

20-100 AH

20-100 AH

20-80 AH

BATTERY VOLTAGE

2 X 12 CELLS 

2 X 15 CELLS 

2 X 55 CELLS 

RATED CURRENT

10 AMP

6 AMP

10 AMPS